Rite Engineering and Manufacturing Corp
Tridicators

UL Listed Emergency Door Switch

According to CSD-1, an emergency boiler room shut off switch is required. (See Below)

“A manually operated remote shutdown switch or circuit breaker shall be located just outside the boiler room door and marked for easy identification. Consideration should be given to the type and location of the switch to safeguard against tampering. If the boiler room door is on the building exterior, the switch should be located just inside the door. If there is more than one door to the boiler room, there should be a switch located at each door. Activation of the emergency shutdown switch or circuit breaker shall immediately shut off the fuel or energy supply.”

- Source: ASME CSD-1 2009