Conductivity setpoint set at “lo” * Factory settings should be changed for 0-6000 microsiemens per when job specific conditions warrant centimeter. To
convert to TDS Changes should be made by the chemical (total dissolved solids)
in PPM treatment specialist in charge of keeping (parts per million) divide by 1.5.
Blowdown conductivity should 5 to 7 times the make-up
water conductivity and no more than 10 times. Intervals between sampling
blowdowns set for once every 4 hours |
 |
* Factory settings should be changes when job specific conditions warrant.
changes should be make by the chemical treatment specialist in charge of keeping
the boiler scale free.
"ADJ" = calibration adjustment refer to "Series 2EZ
Installation of Maintenance Repair Manual" for calibration instructions.
Duration of sampling blowdown set at 3 minutes. |